EC7895C1000/U

Microprocessor-based integrated primary burner control for
automatically fired gas, oil, or combination fuel single burner
applications. Provides level of safety, functional capability and
features beyond conventional controls.

  • Functions include automatic burner sequencing, flame supervision,
    system status indication, system or self diagnostics and troubleshooting.
  • Subbase, amplifier, and prepurge timer are required for operation.
  • Options include PC interface, keyboard display module, DATA
    CONTROLBUS™ MODULE, remote display module, first-out
    expanded annunciator, and COMBUSTION SYSTEM MANAGER™
    software.
  • Five LEDs provide sequence information.
  • Interchangeable plug-in flame amplifiers.
  • Optional local or remote annunciation of operation and fault
    information.
  • Nonvolatile memory retains history files and sequencing status after
    power loss.
  • Optional remote reset capability.
  • Optional report generation. Selectable relight or lockout on loss of
    flame.
  • Airflow switch check.
    Application: On-Off Primary Control with Prepurge
    Interlocks: Selectable
    PrePurge: Determined by ST7800A Purge Timer Card
    Required Components: Q7800 Universal Wiring Subbases, Flame
    Signal Amplifier and ST7800A Plug-in Purge Timer Card
    Frequency: 50 Hz; 60 Hz (±10%)
    Vibration: 0.5 G environment
    Shipping and Storage Temperature Range: -40°F to +140°F (-40°C
    to +60°C)
    Approximate, Dimensions: 5 in. wide x 5 in. high x 5 1/4 in. deep
    with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase
    (127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase
    x 155 mm deep with Q7800B Subbase)
    Weight lb. (kg): 1 lb 15 oz (0.9 kg)
    Approvals, Swiss RE: Acceptable
    Used With: 7800 Series Amplifiers (Except RM7895E1002/U uses
    R7847 ONLY)
    • Model: EC7895C1000/U
    • Voltage 220 to 240 Vac (+10, -15%)
    • Pilot Type: interrupted
    • Delayed Main Valve: Yes
    • Flame Establishing Period – Main: 10 sec
    • Flame Establishing Period – Pilot : 4 or 10 sec